BALANCED FLUES (GAS-FIRED)
|

|

Balanced
Flue Terminal |
A balanced flue is used on the Rayburn 480CD model.
There are a number of important points to
be considered as to where the flue can be situated, so as to comply with current
legislation and good practice.
Places to be avoided are ;-
Underneath windows // close to doorways //
adjacent to obstructions or protruding buildings // discharging into car-ports
and garages, alleyways or public thoroughfares // too close to a facing
obstruction such as a fence.
As this is a condensing appliance, consideration should be given as to the
possible nuisance caused by the natural pluming which will occur from the
terminal.
The flue can only exit straight from the rear of
the Rayburn
to outside: bends are not permitted. Standard flue length 514mm
Optional extension up to 1000mm
No additional extensions are allowed,
beyond these lengths.
The following illustration shows the minimum clearances
required.

| A |
BELOW A GUTTER OR
SANITARY PIPEWORK |
600mm |
H |
VERTICAL FROM
TERMINALS ON THE SAME WALL |
1500mm |
| B |
HORIZONTAL FROM
OPENING, AIR BRICK, WINDOW ETC |
600mm |
I |
HORIZONTAL FROM
TERMINALS ON THE SAME WALL |
750mm |
| C |
ABOVE GROUND OR
BALCONY LEVEL |
300mm |
J |
BELOW AN OPENING,
AIR BRICK, WINDOW ETC |
600mm |
| D |
BELOW EAVES OR
BALCONY |
600mm |
K |
FROM VERTICAL
SANITARY PIPEWORK |
300mm |
| E |
FROM AN INTERNAL OR
EXTERNAL CORNER |
300mm |
|
|
|
| F |
FROM A TERMINAL
FACING A TERMINAL |
1200mm |
|
|
|
| G |
FROM A SURFACE
FACING A TERMINAL |
600mm |
These are minimum dimensions to ensure that the
products of combustion can clear satisfactorily, but they cannot take into
account any special adverse site conditions, such as extra turbulent wind in
exposed regions. e.g. adjacent to cliffs or high hills.
If the flue terminates within 1 metre of plastic
material such as guttering or waste pipes, they must be shielded for protection.
The protective wire
cage must be fitted. (supplied with the Rayburn).
If the flue terminates on a wall which is clad
with combustible material, this must be cut back 50mm beyond the outer edge of
the terminal and replaced by a non-combustible material.
No air for combustion is taken from the room as
the appliance flue-ways etc are room sealed, an alternative name for
this type of appliance.
The ovens are vented naturally.
|